Overview:
The V4055 Gas Valve Actuator, in combination with a VE5000a, V5055 or V5097 Gas Valve, controls the gas supply to commercial and industrial burners. When replacing a V4034 with a V4055, the V5034 gas valve must also be replaced with a V5055 or V5097 gas valve.
Available Model Features:
V4055A1007:
- The V4055 Actuator can be used with the characterized guide model of the V5055 or V5097 Gas Valve to enhance lightoff smoothness.
- The standard model has an opening time of 26 seconds at 60 Hz or 32 seconds at 50 Hz.
- Maximum closing time is one second, which meets code, standard and insurer requirements.
- Maximum Safe Operating Pressure: 5 psi (34 kPa)
- Ambient temperature rating is -40°F to +150°F (-40°C to +66°C) for 60 Hz models and -10°F to +158°F (-23°C to +70°C) for 50 Hz and 50/60 Hz models.
- Standard enclosure meets NEMA 1 (IP30) requirements
V4055D1043:
- Gas Valve actuator with Proof of Closure, 13 Sec, 120V
Product Specifications:
- Damper Shaft: Shaft is 3/8 in. (9.5 mm) square, for use with 7616BR Damper Crank Arm (ordered separately) and with or without damper shaft return spring.
- Maximum Damper Shaft Rotation: 52 angular degrees.
- Maximum Force: 2-11/16 in. (68.3 mm) radius for 7616BR Damper Crank Arm ordered separately (see Accessories section).
- Underwriters Laboratories Inc. Listed: File No. MH1639, Guide No. YIOZ.
- Factory Mutual: Approved